Operator's Manual: Models CB-1500 & CB-2500 (230V / 50 Hz)
9-2
Periodic Burner Inspection
Following initial start up of the burner, you should inspect the operation of the burner periodically--ideally on a
monthly basis. Doing so ensures that the system is functioning efficiently and safely.
Follow these guidelines for inspecting the operation of the burner:
• Visually inspect the flame length through the observation
port; the flame should extend no more than one-half of
the way down the combustion chamber.
-If the flame is diminishing or displays wide
variations, clean the canister filter and check
valve/screen (procedures provided in this
section).
-If the flame is firing too strongly (i.e. flame
touches back and/or side walls of the
combustion chamber), check the air pressure setting (see following guideline).
• Check the air pressure by observing the air gauge; proper air pressure settings are provided in
Section 6. DO NOT overfire the burner; doing so on a continual basis will damage the furnace.
• Check the combustion air band setting for the proper opening and clean away any dust/debris as
necessary. Note that the air band should NEVER be set fully open or closed.
• Check the draft over fire reading as specified in Section 8.
Figure 9A - Burner Component Detail
CAUTION
WHEN OPENING INSPECTION PORT
PORT MAY BE HOT
PROTECT HANDS
WEAR SAFETY GOGGLES
KEEP FACE AWAY
OPEN PORT SLOWLY
I88901
AIR BAND
COMBUSTION
t
s
1
0
s
2
2
0
-
2
4
0
5
0
-
6
0
H
z
3
W
D
a
n
f
o
s
s
T
y
p
e
B
H
O
6
4
N
r
.
0
5
7
H
7
0
3
6
AIR REGULATOR
LOCKING NUT
COVER PLATE
AIR GAUGE
OIL GAUGE
Comments to this Manuals