Operator's Manual: Models CB-1500 & CB-2500 (230 V / 50 Hz)
10-2
Main power ON
sending power to
centrifugal switch
and both high limit
switches.
Burner cable
plugged in.
Green indicator
light ON.
Preheater thermostat activates 450 watt block
heater element and heats the block to 60 °C (140 °F).
INITIAL START-UP
Preheater thermostat cycles 450 watt block
heater element and maintains 60 °C (140 °F)
block temperature.
NORMAL BURNER OPERATION
When block temperature reaches 49 °C
(120 °F) , the F120 proving switch closes
and sends power to the oil primary control.
F120 proving switch remains closed and oil
primary control has power.
Oil primary control checks for
2000+ ohms from cad cell
indicating dark in the combustion
chamber (NO FLAME)
BURNER PRE-IGNITION SEQUENCE
Oil primary control relay closes.
Burner ignition sequence begins.
BURNER IGNITION SEQUENCE
14,000 volt igniter starts,
providing Interupted
(15 sec.) spark at
electrode gap.
Air solenoid
opens.
INITIAL START-UP
Air regulator adjusted to
proper air pressure.
Air sensing switch closes
as it receives more than
0.7 bar (10 psi) of air
pressure.
Pump circuit starts
oil pump.
Yellow indicator
light ON.
Pump circuit opens
oil solenoid.
Air sensing switch
receives power from
centrifugal switch.
INITIAL START-UP
Combustion air band adjusted
for proper combustion air.
Centrifugal switch closes and
sends power to air sensing
switch.
Burner motor starts and
reaches full rpm.
Burner ignites.
Oil primary control
receives <500 ohm signal
from cad cell indicating
proper ignition.
Burner continues to run
until the wall thermostat
is satisfied.
FURNACE HEATING SEQUENCE
Blower switch on combustion
chamber senses temperature
rise as the burner fires.
Blower switch senses ON
temperature of 82 °C (180 °F)
and Blower switch closes.
Blower switch sends power
to motor, and blower starts.
Wall thermostat is
satisfied and T
circuit opens.
Primary control relay
opens and the burner
shuts off.
Blower continues to run to drive
latent heat from the heat exchanger.
Blower switch senses OFF temperature of
71 °C (160 °F) and Blower switch opens.
Blower stops running.
FURNACE COOL DOWN SEQUENCE
Warm air delivered
to heated area.
Hour meter starts.
Wall thermostat calls for heat and
closes 24V thermostat.
FLOW CHART
230 V / 50 Hz
I88849